450/750V PVC Insulated PVC Sheathed AL-PlasticTape Screened Control Cable

6-10KV YJV32-Copper Conductor XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable 01

APPLICATION
Copper Conductor PVC Insulated PVC Sheathed Aluminium Plastic Tape Screened Rigid Control Cable (KVVP3) is mainly used for system connection wire of control, signal, protection or measuring for rated voltage up to and including 450/750V.

CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.

18

 

 

BASIC INFORMATION
Code Name
KVVP3
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation/AL-Plastic Tape Screened/PVC Sheath

CONSTRUCTION
Conductor
Preferred Number of cores:
4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52,61
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/A according to IEC
Metallic Screened
Aluminium Plastic compound Tape
Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST1 according to IEC
Other special application cable can be provided upon requests:
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke ( lszh ),as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant,Water proof series and so on.

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Max.temperature of conductor under short circuit-(Max.Duration 5 sec.)
PVC Insulated:160℃
Preferred Permissible bending radius
For non-armoured PVC insulated cable not less than: 12 times of cable diameter

Nominal Cross Sectional Area(mm²)No. of CoresClass of ConductorMax.D.C.Resistance at 20℃(Ω/km):PlainMax.D.C.Resistance at 20℃(Ω/km):Metal-coated
0.5////
0.754-61124.24 24.8
14-61118.118.18
1.54-61112.112.2
2.54-6117.417.56
44-1414.614.7
64-1413.083.11
104-1021.831.84