18/30KV YJLHV22-Aluminum Alloy Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable

Aluminum Alloy Conductor(AAAC) XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable 3.6/6KV-26/35KV
Aluminum Alloy Conductor(AAAC) XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable 3.6/6KV-26/35KV

APPLICATION
YJLHV22-Aluminum Alloy Conductor XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable.
AAAC XLPE STA Armoured Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJLHV22
Rated Voltage (Uo/U)
18/20KV、18/30KV
Cable Structure
Aluminum Alloy Conductor/XLPE Insulation/PVC Inner Sheath/Steel Tape Armoured/PVC Outer Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyvinyl Chloride) according to IEC
Metal Screen
Copper Tape Screen
Armoured Layer
Steel Tape

CHARACTERISTICS
Conductor Temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit Temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation Temperature
Ambient temperature under installation shall not be below 0℃
Minimum Bending Radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥10D
For Single Core Cable————————————-≥15D

Nominal Cross Sectional Area(mm²)No.of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
501835.41760
701838.61910
951840.12100
1201841.82290
1501843.42490
1851845.32690
2401847.63030
3001850.23300
4001853.43880
50018574390
6301861.25030
503875.16250
703878.76910
9538847620
1203887.58870
1503891.39580
1853894.910450
24038100.311590
30038105.612850
40038112.814410
50038119.316330
63038128.918970