3.6/6KV YJV32-Copper Conductor XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable

3.6-6KV YJV32-Copper Conductor XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable 01

APPLICATION
YJV32- Copper Conductor XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable.
Copper XLPE SWA Armoured  Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJV32
Rated Voltage (Uo/U)
3.6/6KV
Cable Structure
Copper Conductor/XLPE Insulation/Steel Tape Armoured/PVC Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Metal screen
Copper Tape Screen
Armoured Layer
Steel Tape

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥15D
For Single Core Cable————————————-≥20D

Nominal Cross Sectional Area (mm²)NO. of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
2512.524.71340
3512.525.81490
5012.527.21720
7012.528.82010
9512.530.62350
12012.532.12680
15012.534.93070
18512.536.53480
24012.639.14140
30012.841.94840
4001345.66320
50013.249.37470
63013.253.18940
2532.542.73620
3532.546.24140
5032.549.34860
7032.552.95770
9532.5576870
12032.560.47870
15032.564.29090
18532.567.810460
24032.675.113380
30032.881.315680
4003389.519320
50033.297.623060
63033.2105.727690