12/20KV YJLHV32-Aluminum Alloy Conductor XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable

Aluminum Alloy Conductor(AAAC) XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable 3.6/6KV-26/35KV

APPLICATION
YJLHV32 – Aluminum Alloy Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed Power Cable
AAAC XLPE SWA Armoured Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJLHV32
Rated Voltage (Uo/U)
12/20KV
Cable Structure
Aluminum Alloy Conductor/XLPE Insulation/PVC Inner Sheath/Steel Wire Armoured/PVC Outer Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyvinyl Chloride) according to IEC
Metal Screen
Copper Tape Screen
Armoured Layer
Steel Wire

CHARACTERISTICS
Conductor Temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit Temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation Temperature
Ambient temperature under installation shall not be below 0℃
Minimum Bending Radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥10D
For Single Core Cable————————————-≥15D

Nominal Cross Sectional Area(mm²)No.of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
3512.532.21820
5012.533.61980
7012.535.22150
9512.5372370
12012.538.52550
15012.540.22770
18512.541.82990
24012.645.43690
30012.847.94110
4001351.34690
50013.254.65280
63013.258.46010
3532.560.75330
5032.563.85810
7032.567.36430
9532.572.87890
12032.576.18580
15032.579.99410
18532.583.510180
24032.68911420
30032.894.312720
40033101.514710
50033.2108.616710
63033.2116.719050