18~30KV YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable

18-30KV YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable 01

APPLICATION
YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable.
Copper XLPE Power Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJV
Rated Voltage (Uo/U)
18/20KV, 18/30KV
Cable Structure
Copper Conductor/XLPE Insulation/PVC Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Metal screen
Copper Tape Screen

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥15D
For Single Core Cable————————————-≥20D

Nominal Cross Sectional Area (mm²)NO. of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
351831.91240
501833.31560
701834.91840
951836.72140
1201838.22450
1501839.92790
1851841.53200
24018443800
3001846.34460
4001849.65530
5001852.86160
6301856.48020
503868.45290
703872.56240
953875.97360
1203879.48350
1503882.69520
1853886.410830
2403891.412810
3003896.714920
40038103.818110
50038111.120990
63038119.225290