26/35KV YJLHV22-Aluminum Alloy Conductor XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable

Aluminum Alloy Conductor(AAAC) XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable 3.6/6KV-26/35KV
Aluminum Alloy Conductor(AAAC) XLPE Insulated PVC Sheathed Steel Tape Armoured Power Cable 3.6/6KV-26/35KV

APPLICATION
YJLHV22-Aluminum Alloy Conductor XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable.
AAAC XLPE STA Armoured Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJLHV22
Rated Voltage (Uo/U)
26/35KV
Cable Structure
Aluminum Alloy Conductor/XLPE Insulation/PVC Inner Sheath/Steel Tape Armoured/PVC Outer Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyvinyl Chloride) according to IEC
Metal Screen
Copper Tape Screen
Armoured Layer
Steel Tape

CHARACTERISTICS
Conductor Temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit Temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation Temperature
Ambient temperature under installation shall not be below 0℃
Minimum Bending Radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥10D
For Single Core Cable————————————-≥15D

.

Nominal Cross Sectional Area(mm²)No.of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
50110.543.72320
70110.545.22480
95110.547.12690
120110.548.72860
150110.550.53090
185110.5523305
240110.554.73660
300110.557.14040
400110.560.54520
500110.565.65290
630110.569.25910
50310.588.67820
70310.5928430
95310.586.39270
120310.599.79970
150310.5103.310730
185310.510711500
240310.5112.512800
300310.5117.714100
400310.5125.116080