300/500V Nylon Sheathed Rigid Conductor Flat PVC Cable

300-500V PVC Insulated Nylon Sheathed Rigid Conductor Flat Cable Drawing

APPLICATION
Rigid Copper Conductor Nylon Sheathed PVC Insulated Flat Cable (BVNVB) is mainly used at Fixed-wiring for construction.

CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.

18

 

 

BASIC INFORMATION
Code Name
BVNVB
Rated Voltage (Uo/U)
300/500V
Cable Structure
CU/PVC Insulation/Nylon Sheathed/PVC Sheathed

CONSTRUCTION
Conductor
Number of conductors:2,3 or other your requirement.
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/C according to IEC
Inner Sheathed
Nylon
Over Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST4 according to IEC

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Nylon Wire’s advantage
Nylon Sheathed Rigid Conductor Flat PVC Cable is provided with excellent thermal stability, better machanical strength,surface strength,thermal distortion resistance, impact strength,beneling strength,a brasion-resistane,chemical resistance and geg-lubrication,as well as better machineoil resistance and gusoline resistance,gelf-lubrication will make installation easier and help reducing wire damage in the course of conduit installation.

Nominal Cross Sectional Area (mm²)NO. of CoresClass of ConductorMax.Average Overall Diameter (mm)
0.75214.5x6.8
1214.7x7.3
1.5214.9x7.8
2.5215.6x8.9
4216.2x10.0
4226.3x10.3
6217.2x11.8
6227.4x12.3
10218.9x15.1
10229.3x15.6
0.75314.5x9.2
1314.7x9.8
1.5314.9x10.6
2.5315.6x12.2
4316.4x14.6
4326.6x14.6
6317.2x16.5
6327.4x17.2
10318.9x21.2
10329.3x22.2