450/750V PVC Insulated Steel Wire Armoured PVC Sheathed Control Cable
APPLICATION
Copper Conductor PVC Insulated Steel Wire Armoured PVC Sheathed Rigid SY Control Cable is mainly used for system connection wire of control,signal,protection or measuring for rated voltage up to and including 450/750V.
CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.
BASIC INFORMATION
Code Name
KVV32
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation/Steel Wire Armoured/PVC Sheathed
CONSTRUCTION
Conductor
Preferred Number of cores:
2,3,4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52,61
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/A according to IEC
Armoured
Steel Wire
Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST1 according to IEC
Other special application cable can be provided upon requests:
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke,as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant, Water proof series and so on.
CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Max.temperature of conductor under short circuit-(Max.Duration 5 sec.)
PVC Insulated:160℃
Preferred Permissible bending radius
For non-armoured PVC insulated cable not less than: 12 times of cable diameter
Nominal Cross Sectional Area(mm²) | No. of Cores | Class of Conductor | Max.D.C.Resistance at 20℃(Ω/km):Plain | Max.D.C.Resistance at 20℃(Ω/km):Metal-coated |
---|---|---|---|---|
0.5 | / | / | / | / |
0.75 | 19-61 | 1 | 24.24 | 24.8 |
1 | 19-61 | 1 | 18.1 | 18.18 |
1.5 | 7-61 | 1 | 12.1 | 12.2 |
2.5 | 7-61 | 1 | 7.41 | 7.56 |
4 | 4-14 | 1 | 4.61 | 4.7 |
6 | 4-14 | 1 | 3.08 | 3.11 |
10 | 4-10 | 2 | 1.83 | 1.84 |