8.7~15KV YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable

8.7-15KV YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable 01

APPLICATION
YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable.
Copper XLPE Power Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV.

CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.

18

 

 

BASIC INFORMATION
Code Name
YJV
Rated Voltage (Uo/U)
8.7/10KV、8.7/15KV
Cable Structure
Copper Conductor/XLPE Insulation/PVC Sheath

CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Metal screen
Copper Tape Screen

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable————————————-≥15D
For Single Core Cable————————————-≥20D

Nominal Cross Sectional Area (mm²)NO. of CoresNominal Insulation Thickness(mm)Approx Overall Diameter(mm)Cable Weight Max(kg/km)
2514.522696
3514.523819
5014.524.5970
7014.526.21191
9514.527.91493
12014.529.51760
15014.531.12085
18514.532.82391
24014.535.32873
30014.537.73657
40014.540.94571
50014.544.45692
63014.5486945
2534.5452217
3534.547.32616
5034.550.33144
7034.553.83879
9534.557.64872
12034.560.95753
15034.564.56837
18534.568.17900
24034.573.39719
30034.578.411862
40034.585.314795
50034.59318381
63034.5100.722396